SOLLICH 1503 CPM-LP
Cathodic Protection Microstation v.Low Power, for fuel tanks, Imax-1mA-100mA

Microstation of Cathodic Protection with very low power consumption, dedicated to systems operating in a wide range of ambient temperatures.

Controlled by a microprocessor.

All available operating modes and functions.

U: 12 – 24 Vdc

RS 485 communication interface.

Energy efficiency up to 96%.

Documentation

and technical data

Description

The SOLLICH 1503 CATHODIC PROTECTION MICROSTATION  is a device intended for the cathodic protection of metal and reinforced concrete structures. This protection consists in providing the appropriate protection potential of the structure by forcing current in the anode system – a protected construction.

The SOLLICH 1503 CATHODIC PROTECTION MICROSTATION device works in a two-electrode system – without a reference electrode, or a three-electrode system in combination with a reference electrode.

The device enables programming the value of the polarization current Ip (cathodic protection current) or the turn-on potential Eon or turn-off potential Eoff, relative to the reference electrode Eo (measuring) and maintains these values during operation.

The device measures the value of the polarization current (cathodic protection) Ip, the turn-on potential Eon or turn-off potential Eoff relative to the reference electrode Eo, and the anode-cathode voltage Ua.

The station can operate without forced cooling in ambient temperatures up to 50 °C.

Device functions

  • Operation in galvanostatic mode – current excitation and potentiostatic mode – potential excitation,
  • Multiple operating modes and configuration functions for a wide range of applications,
  • Programmable current and potential setting,
  • Automatic precision measurements,
  • LCD alphanumeric display with backlight, information on the current operating status of the station,
  • Cyclic recording of measurements performed in the non-volatile station memory,
  • Signaling “Control of the potential range” with colors: green, red and yellow-orange,
  • Programming the scope of potential control,
  • The ability to enable / disable signaling “Potential range control”,
  • Generating alarm signals,
  • High energy efficiency,
  • Remote reading and adjustment of operating parameters, communication with external devices, support for the ModBus protocol,
  • Easy installation on a DIN rail, simple commissioning, easy operation,
  • Software for reading results from station memory and for setting protection parameters.

Technical data

Parameter:UnitsMin.Max.
Output current  Ip

Model 24-20-LP

Model 24-50-LP

Model 24-100-LP

mA

mA

mA

0,1

0,5

2

20

50

100

Output voltage Ua

Us = 12V

Us = 15V

Us = 24V

V

V

V

0,3

0,4

0,5

9

11

18

 *) Measurement error Ip: 1,5 % (full range).

**) Measurement error pot. Eon i Eoff: 10 mV +/-2,5 %.

***) Programmable time Toff/Ton (On/Off) current Ip.

****) Programmable time deley measurement Eoff.

*****) Communication interface RS 485 MODBUS.

******) Memory for 10 years of recording.