SOLLICH 2103 SOK
Cathodic Protection Station for fuel tanks, Imax=4A

Cathodic Protection Station with low power consumption, dedicated to systems operating in a wide range of ambient temperatures.

Application for cathodic protection of:

  • different types of pipelines
  • steel constructions
  • tanks for liquid and gas fuels

Controlled by a microprocessor.

All modes and functions are available.

Power supply: 12 – 24 Vdc

RS 485. communication interface

SKU: 0-2-1-1 Categories: ,

Documentation

and technical data

Description

Cathodic Protection Station SOLLICH 2103 CATHODIC PROTECTION STATION is designed for cathodic protection of metal structures, built locally as well as in a large area, on its surface, in water, with good insulation in relation to the ground. In particular, these are all kinds of liquid and gaseous fuel tanks, pipelines and gas pipelines.

The Cathodic Protection Station works in a three-electrode system with a reference electrode or in a two-electrode system without this electrode. The -/K cathode and the Ku terminal are connected to the protected structure.

The OK station (Cathodic Protection) enables temporary switching off of the protection current.
The OK station enables the implementation of the described task in an automatic way by adjusting the operating parameters so as to force the set value of current or potential. The device has the ability to manually and remotely change the operating mode and parameters.

The Cathodic Protection Station measures the following parameters:

Ip – structure polarization current.
Uak – anode voltage – construction.
Eon – switching potential of the structure.
Eoff – the structure’s shutdown potential.
Uac_on – RMS value of AC interference signals occurring on the structure.
Uac_off – RMS value of AC interference signals occurring on the structure.
E(t) – Measurement of the structure potential time course.

The SOLLICH 2103 CPS station requires a DC voltage supply with parameters depending on the version
execution.

version: 24-1000 (Us = 12 … 28V; Ip_max = 1000 mA)
version: 24-2000 (Us = 12 … 28V; Ip_max = 2000 mA)
version: 24-4000 (Us = 12 … 28V; Ip_max = 4000 mA)
version: 48-1000 (Us = 24 … 52V; Ip_max = 1000 mA)
version: 48-2000 (Us = 24 … 52V; Ip_max = 2000 mA)

Features of the device

  1. Operation in
    • galvanostatic mode – forcing a constant protection current
    • potentiostatic mode – forcing a constant protection potential
  2. Variety functions that allow configuration for a wide range of applications
  3. Possibility of software disconnection of the station
  4. Current and potential regulation
  5. Automatic measurements
  6. Built-in accurate and robust measurement systems
  7. Registration of structure potential changes over time
  8. Analog-digital implementation of regulation and control systems
  9. Alphanumeric LCD display visible in the dark
  10. Information on the current operating status, alarm signals
  11. Built-in external logic inputs to control the operation of the station
  12. Built-in external logic outputs to control the operation of other devices in the OK installation
  13. Registration of protection parameters and signal values in non-volatile memory
  14. High energy efficiency
  15. Remote reading of operating parameters
  16. Socket for communication with external devices – RS485
  17. Modbus protocol support
  18. Made in accordance with the EMC directive
  19. Wide operating temperature range
  20. Easy DIN rail installation
  21. Simple start-up, easy operation

Technical Data

1. TECHNICAL PARAMETERS

No.Output electrical parameters of the device:UnitMin valueMax valueNotes
1. Station power supply voltage 0V, UsV24 or 48Depending on model
Minimum output current of the Station power supplyFor model:SOLLICH 2103 CPS / 24-1000A2Power supplies meeting the condition:24V-45W,
For model:SOLLICH 2103 CPS / 24-2000A2.5Power supplies meeting the condition:24V-60W,
For model:SOLLICH 2103 CPS / 24-4000A5Power supplies meeting the condition:24V-120W,
For model:SOLLICH 2103 CPS / 48-1000A2Power supplies meeting the condition:48V-100W,
For model:SOLLICH 2103 CPS / 48-2000A2.5Power supplies meeting the condition:48V-120W,
2.Protection output current – Ipnominal current – programmable valuemA2.51000Model 24-1000
Current measurement inaccuracy Ip%+mA2% +/- 2.5mA
Protection output current – Ipnominal current – programmable valuemA52000Model 24-2000
Current measurement inaccuracy Ip%+mA2% +/- 5mA
Protection output current – Ipnominal current – programmable valuemA104000Model 24-4000
Ip current measurement inaccuracy%+mA2% +/- 10mA
Protection output current – Ipnominal current – programmable valuemA2.51000Model 48-1000
Current measurement inaccuracy Ip%+mA2% +/- 2.5mA
Protection output current – Ipnominal current – programmable valuemA52000Model 48-2000
Current measurement inaccuracy Ip%+mA2% +/- 5mA
3.Potential programming range Ep, on terminals Eo-KpV0-5
4.Potential measurement range Ep,on terminals Eo-KpV0+/-7V 
5.Inaccuracy of Ep potential measurement mV+%+/- 2mV +/- 0.5%
6.Measurement range of rms value of AC disturbances on Eo-Kp terminalsVrms07 Vac
7.Potential measurement inaccuracy EpmV+%+/- 3mV +/- 0.5%
8.Eo reference electrode input circuit surge limitV+/- 20VImax=2A@ t=10/1000us pulse
9.Serial input resistance of overvoltage limit circuitOhms10k
10.Voltage measurement range U_ameasured on output terminals Au-KuV0+Us – 4
11.Voltage measurement inaccuracy U_aV+%+/- 0.2V +/-2%
12.Eo reference electrode input circuit surge limitV+/- 33VImax=5.5A@ t=10/1000us pulse
13.Anode circuit series output resistanceOhms0.1
14.Current consumption by the station without installation circuits OK:- for display on – for display off – for display on – for display off  mAmA 6958 7362 @ Us = 24Vdc 
 mAmA 4938 5746 @ Us = 48Vdc 
15.Interval of writes to non-volatile memoryminutes120,000
16.Maximum number of samples saved to non-volatile memoryresults196,000> 22 years for 1/60 minute recording
17.Fuse type: 5×20 T250V Housing station protectionAWTAT 1.6A/250VModels: 24-1000 and 48-1000;
AWTAT 3.15A/250VModel 24-2000; Model 48-2000
AWTAT 5A/250VModel 24-4000;

 2. GENERAL PARAMETERS

No.General:UnitValue
1.dimensions width x height x depthmm105 x 90 x 65
2.weightkg.approx. 0.42
3.maximum ambient temperature at full load power°C-20 to +45
4.maximum ambient relative humidity%95

 3. LIST OF COMPONENTS

No.designationdescriptionSOLLICH 2103 CPS included
1.SOLLICH 2103 CPSSOLLICH 2103 CPS stationstandard
2.DTR SOLLICH 2103 CPSOperational and technical documentation for SOLLICH 2103 CPS Stationstandard
3.SOLLICH 2103 CPS GuaranteeSOLLICH 2103 CPS Guaranteestandard
4.Power adapterDIN rail adapter -U output = 24 or 48 Vdcoptional
5. Sollich_CPSCD or flash drive with installation program for reading archive dataoptional
6.Sollich_CPSCD or flash drive with the installation program for programming the station via Modbus link.optional
7.SOLLICH 1695 CICGPS circuit breaker generating a current interruption signal to the SOLLICH 2103 CPS Stationoptional
8.SOLLICH 1498 USB-RS485USB<->RS485 converteroptional
9SOLLICH 1900 CP-SYSHousing for mounting the SOLLICH 2103 station, current booster, SOLLICH 1695 CIC GPS Chopper, power supply, overcurrent and overvoltage protections and other accessories on a DIN rail.optional

 